Tip The arrow on the current transformer must point towards the MultiPlus-II, and the cable must not be shortened or extended — it is calibrated together with the transformer.
Victron Help Centre
AC current measurement

Current transformer for MultiPlus-II

A split-core transformer fitted around the phase conductor. It allows MultiPlus-II to measure current flowing to and from the mains without passing it through the inverter — so PowerControl, PowerAssist and self-consumption optimisation work where a full energy meter is not needed.

  • 100 A or 400 A
  • 50 mV ratio
  • 1, 5 or 20 m cable
  • single phase
  • without cutting into the installation
Measurement range100 / 400 A
Output signal50 mV
Cable length1, 5 or 20 m
Number of phases1 per transformer
Based on the datasheet “Current Transformer for MultiPlus-II & MultiPlus 20 kW” and the MultiPlus-II manual. Independent description. Sources
What it is for

MultiPlus-II sees current that does not flow through it

MultiPlus-II measures current with its own internal transformer — but only the current passing through its AC input. In a parallel arrangement with the mains, some loads are connected directly to the supply, so the inverter does not know how much energy the whole house is using.

An external transformer is fitted around the phase conductor before the circuits are split. MultiPlus-II then knows how much current flows to and from the mains and can use this to limit import (PowerControl), add power from the battery (PowerAssist) and increase self-consumption.

  • it is fitted around the existing conductor — no need to cut into the installation,
  • cheaper and quicker to install than a DIN-rail energy meter,
  • useful where there is no room left in the consumer unit for a meter.
Exploded 100 A current transformer — split core for a phase cable
Split core with hinge. It encloses the phase conductor and measures the current flowing in it — without interfering with the circuit.
Features

What external current measurement gives you

Current to and from the mains

Based on the measurement, MultiPlus-II knows which direction current is flowing through the supply and how much — even when some loads are outside its AC output.

PowerControl and PowerAssist

External measurement extends both functions: in 3 kVA models to 50 A, and in 5 kVA models to 100 A. The inverter adds battery power only when the supply is genuinely close to its limit.

Higher self-consumption

In a parallel arrangement with the mains, the measurement lets you use your own energy instead of exporting it to the grid, and if needed completely prevent export.

Installation without modifications

The core opens and clips around the existing phase conductor. There is no need to cut the installation or route conductors through the inverter.

System with an external transfer switch

In a three-phase system with an external transfer switch, the transformer is mandatory — one per phase, connected to the master unit of that phase.

Two connection types

Newer MultiPlus-II and MultiPlus 20 kW models have a two-wire terminal block; older units have a jack socket. There is a separate transformer version for each.

Three cable lengths

1 m, 5 m and 20 m — choose according to the distance between the distribution board and the inverter. The cable must not be shortened or extended.

Two ranges

The 100 A version is for typical installations and the 400 A version is only for systems with an external transfer switch. Both provide a 50 mV output signal.

Versions

Which transformer for which inverter

Close-up of 100 A current transformer — marking SCT013 100A : 50 mA
100 A : 50 mA. The standard version for newer MultiPlus-II models and for MultiPlus 20 kW — with leads terminated with ferrules.
Current transformer in jack-plug version for older MultiPlus-II models
Jack plug version. For older MultiPlus-II units that have a socket instead of a terminal block.
400 A current transformer for systems with an external source switch
400 A : 50 mA. Only for systems with an external transfer switch, with a 10 m cable.
ModelCable lengthConclusionWhat it is for
100 A : 50 mA1 m, 5 m or 20 mwire endsnewer MultiPlus-II models and the MultiPlus 20 kW
100 A : 50 mA1 m, 5 m or 20 mjack plugolder MultiPlus-II models with a socket
400 A : 50 mA10 mwire endsMultiPlus-II in a system with an external transfer switch (firmware s99)

Before ordering, check which connection your inverter has: newer models have a two-wire terminal block labelled EXT and COM, older ones have a jack socket. The 400 A version has only one use: a system with an external transfer switch, where it replaces the internal transfer switches of the individual units.

Current transformer with long cable — 20 m version
The length is chosen to suit the installation. A 20 m cable lets you place the inverter far from the distribution board — but you must not shorten it.
Typical setup

How to connect the current transformer

The transformer clips onto the shore power phase conductor, and its wires go to the external current measurement terminals in the MultiPlus-II. The arrow on the casing must point towards the inverter. Hover over or touch the diagram element. Illustrative diagram.

50 mV Shore power Transformer MultiPlus-II Loads Battery
direct current (DC)alternating current (AC)communication
Hover over the diagram element or tap it.
  1. Mounting locationShore power phase conductor, before the circuits are split.
  2. DirectionThe arrow on the transformer points towards the MultiPlus-II.
  3. Newer modelsRemove the link, red wire to EXT, white to COM — the transformer is polarity-sensitive.
  4. Older modelsThe jack plug is inserted into the external current measurement socket.
  5. CableDo not shorten or extend it — it is calibrated together with the transformer.
Installation

Four things you need to get right

Arrow direction

The arrow on the transformer casing must point towards the MultiPlus-II. If fitted the wrong way round, the sign of the measurement is reversed, so the inverter “sees” energy flowing in the wrong direction.

Do not shorten the cable

The cable is calibrated together with the transformer — shortening or extending it changes the measurement result. Choose the length when you buy it: 1, 5 or 20 m.

Link and polarity

In newer MultiPlus-II models, first remove the link from the external measurement terminals. The transformer is polarity-sensitive: red wire to terminal EXT, white to COM.

  • One phase per transformer. In a three-phase system with an external transfer switch, you need a separate transformer for each phase, connected to the master unit for that phase.
  • Work in the distribution board must be carried out by a qualified person, with the power isolated. The transformer is fitted around an insulated conductor — not a bare core.
  • The 400 A version may be used only in a system with an external transfer switch — it has no use in a standard installation.
Open split core current transformer fitted around the cable
Clipped onto the conductor. The core must close fully — if left open, it will not measure current correctly.
What to choose

Transformer or energy meter

This sheet

Current transformer

The simplest solution: clip it onto the conductor and connect it directly to the inverter. It measures current only and only on one phase, but it does not require space in the distribution board or separate communication.

100 A · one phase
Full measurement

Energy Meter VM-3P75CT

An energy meter measures current and voltage, supports one-phase and three-phase systems, counts energy and sends data to the GX device via VE.Can or Ethernet. VM-3P75CT meter datasheet.

power, energy, 3 phases
Built-in GX

MultiPlus-II GX

If you are just building the system, an inverter with a built-in GX device makes it easier to expand with an energy meter and to monitor it in VRM. MultiPlus-II GX datasheet.

inverter + GX
Limitations

What the transformer cannot do

  • One phase only. The manufacturer provides for single-phase measurement; in a three-phase system with an external transfer switch, you need a separate transformer for each phase.
  • It measures current, not voltage. It is not a substitute for an energy meter: it does not provide reactive power, power factor or energy used in kilowatt-hours.
  • Lower accuracy than a dedicated energy meter, especially at low currents.
  • Fixed cable length — shortening or extending it is not permitted, because it changes the calibration.
100 A current transformer with cable and plug for the MultiPlus-II
A simple substitute for a meter. Where all you need is to know the direction and magnitude of current, the transformer does the job more cheaply and quickly.
Diagnostics

Symptom and what to do about it

The inverter shows flow in the wrong direction

The transformer is fitted the wrong way round, or the wires are swapped. The arrow on the casing must point towards the MultiPlus-II, the red wire goes to terminal EXT, the white to COM.

No measurement despite being connected

In newer MultiPlus-II models, you must first remove the link from the external current measurement terminals — while it is still there, the inverter will not read the signal from the transformer.

The reading differs from the utility meter

The transformer is less accurate than an energy meter, especially at low currents. Also check that the cable has not been shortened and that the core closes fully.

PowerAssist responds too late or too early

Check that the transformer is on the correct conductor — it must be the shore power phase conductor before the circuits are split, not an individual load circuit.

The three-phase system does not work correctly

In a configuration with an external transfer switch, each phase needs its own transformer, connected to the master unit for that phase.

The plug does not fit the inverter

Newer models have a terminal block and require the version with wire ends; older ones have a jack socket. These are two different versions of the same transformer.

Questions

Frequently asked questions about the current transformer

Why does the MultiPlus-II need an external transformer?

In a parallel system with the grid, the inverter’s internal transformer cannot measure current flowing to and from the grid, because some loads are outside its AC output. The external transformer provides that measurement and allows PowerControl, PowerAssist and self-consumption optimisation to work.

How do you orient the transformer?

The arrow on the casing must point towards the MultiPlus-II. The transformer is also polarity-sensitive: red wire to terminal EXT, white to COM.

Can I shorten a cable that is too long?

No. The cable is calibrated together with the transformer, so shortening or extending it is not an option. Choose the length when you buy it: 1 m, 5 m or 20 m.

Which version should I buy for my inverter?

For newer MultiPlus-II models and the MultiPlus 20 kW — the version with wire ends, connected to a terminal block. For older MultiPlus-II units — the version with a jack plug.

What is the 400 A version for?

Only for systems in which an external transfer switch replaces the internal transfer switches of the individual MultiPlus-II units. It has no use in a standard installation.

Can the transformer replace an energy meter?

Only where knowing the current is enough. It does not measure voltage, is less accurate than a meter (especially at low currents) and supports one phase. A full picture is provided by Energy Meter VM-3P75CT.

Do I need to modify the installation?

No. The core opens and clips around the existing phase conductor, so there is no need to cut the circuit or route wires through the inverter. The work in the distribution board itself should be done by a qualified person.

What is the output signal?

50 mV at rated current — the same for the 100 A and 400 A versions. The signal goes directly to the inverter’s external current measurement input.

Content compared with Victron Energy documentation (datasheets and manuals) — current as of 20 September 2026. Report a content error · Correction log