Tip Inverter RS Smart Solar has no AC input or mains charger — a generator is connected through a separate battery charger.
Victron Help Centre
Off-grid inverter · 48 V · MPPT

Inverter RS Smart Solar 48/6000

A 48 V / 6 kVA inverter with a built-in 450 V MPPT solar charge controller and bidirectional DC-DC converter. The panels are connected directly to the inverter, and surplus PV power charges the battery. For off-grid installations — the unit has no AC input or mains charger.

  • 48 V
  • 230 V · 6 kVA
  • MPPT 65–450 V
  • 11 kg
  • VE.Can · Bluetooth
Continuous power (25 °C)4800–5300 W
PV power (depending on version)4 or 6 kW
Total charging100 A
Parallel operationup to 12 units · 3 phases
Based on the Inverter RS Smart Solar 48/6000 datasheet, the manufacturer’s manual (online version) and the product page. Independent description. Sources
What it is for

Inverter and solar charge controller in one housing

Inverter RS Smart Solar combines three functions: a 230 V pure sine wave inverter, a bidirectional DC-DC converter and an MPPT solar charge controller. The converter charges the battery when there is excess from the panels, or draws energy from it when needed. The manufacturer intends it for off-grid installations that need 230 V.

You can also charge the battery from a PV inverter connected to the AC output (up to 5000 W). A generator requires a separate battery charger — the inverter itself has no AC input.

  • full galvanic isolation between the panels and the battery,
  • built-in PV isolator on the underside of the enclosure,
  • thanks to high-frequency technology it is light (11 kg); also quiet in operation.
Inverter RS Smart Solar left side — black connection base
425 × 440 × 125 mm, 11 kg. Vertical wall mounting, with 30 cm free space above and below the unit.
MPPT versions

Two 3 kW trackers or one 4 kW?

Manufacturer documents describe two controller versions

The current datasheet and the data table in the manual state two PV inputs of 3 kW each (6 kW total, 12 A per tracker). The product page describes 4 kW MPPT, and the manual text mentions a 4000 W limit (80 A at a 50 V battery) and a model with one tracker — most likely this is the same version. The product code PIN482601000 is the same everywhere, and the manufacturer does not say how to distinguish them.

DatasheetProduct page
MPPT power2 × 3000 W4000 W
PV operating current12 A per tracker18 A
PV Isc16 A30 A (reverse polarity protection 20 A)
PV voltage65–450 V, 120 V start65–450 V per table (80–450 V in the description)

The manual gives 12 A operating current for each tracker and protection up to 16 A; according to it, 30 A is the absolute maximum with correct polarity, outside the specification. The manufacturer’s photos show the enclosure marked “MPPT 450|80” and “Maximum charge current: 80A”, which matches the 4 kW version. Before selecting panels, check the nameplate and the data in VictronConnect (the STATUS screen shows the MPPT controller model). In the single-tracker version, several PV connectors are internally linked to one tracker — the strings should have the same number of the same type of panel.

Inverter RS Smart Solar 48|6000 — front with display, manufacturer photo with MPPT 450|80 marking
Front marking. In the manufacturer’s photo: “Inverter RS Smart Solar 48|6000”, “MPPT 450|80”, and below that maximum charge current 80 A and PV voltage 450 V — this nameplate is worth checking when selecting panels.
Features

What Inverter RS Smart Solar can do

6 kVA inverter

Continuous current 25 A AC. Peak 9 kW for 3 s and 7 kW for 4 minutes. With MPPT power, continuous power at 52 V and 25 °C rises by about 10%, to 5,800 W.

450 V MPPT

Starts at 120 V, operating range 65–450 V. Fast maximum power point tracking algorithm and built-in PV isolator.

Charging up to 100 A

From panels and from the inverter on the AC output, up to 100 A in total (above 60 V the current drops). Algorithm: bulk, absorption, float, optional equalisation.

AC-coupling

An inverter on the AC output (up to 5,000 W) charges the battery; Inverter RS limits it by raising the frequency. This allows the battery to charge to around 95%.

Up to 12 units

Up to 12 units in parallel via VE.Can, in three-phase up to 4 per phase — star only. You can mix solar and non-solar versions; in three-phase at least 3 units, firmware from v1.13.

PV insulation monitoring

Before start-up, insulation test of the panels to earth (threshold 100 kΩ) and 30 mA leakage protection. If there is an insulation fault, the inverter disconnects the AC output and the MPPT continues charging.

Display and Bluetooth

The display shows battery, inverter and controller parameters; configuration in VictronConnect. GX via VE.Can, GlobalLink 520 via VE.Direct.

Relay and inputs

Programmable relay (4 A up to 35 V DC, 1 A up to 70 V DC), two digital inputs, temperature sensor and voltage sense.

smallBMS / 2-wire BMS

The remote input accepts signals from the BMS: “allow to discharge” switches off the inverter, “allow to charge” — charging from the panels.

Inverter RS Smart Solar with open connection compartment — fans, battery and AC terminals, PV inputs
Connection compartment. Two screws at the bottom release the cover. Battery terminals on the left, MC4 panel connectors, and on the underside the main switch (left) and PV isolator (centre).
Inverter RS Smart Solar left side — black connection base
Wall enclosure. All cables enter from below, through the black base with the connection compartment.
Inverter RS Smart Solar right side
Front display. Shows battery, inverter and controller parameters; the same data are visible in VictronConnect.
Technical data

Main specifications

Inverter
Battery voltage38–62 V (start at 41 V, disconnect at 65.5 V)
Output230 V ±2%, 50 Hz ±0.1% (60 Hz possible)
Continuous power25 °C: 4,800 W at 46 V → 5,300 W at 52 V; 40 °C: 4,500 W; 65 °C: 3,000 W
Peak power9 kW for 3 s, 7 kW for 4 min
Continuous / short-circuit current25 A AC / 45 A
Efficiency96.5% at 1 kW, 94% at 5 kW
No-load consumption20 W
Low battery voltageshutdown 37.2 V, restart 43.6 V (adjustable)
PV and charging (datasheet)
PV voltagemax. 450 V, start 120 V, MPPT 65–450 V
PV current12 A operating, Isc 16 A
PV power6,000 W total, 3,000 W per tracker
PV insulationpre-start test, 100 kΩ threshold; 30 mA leakage
AC-couplingup to 5,000 W from the inverter on the AC output
Total charging100 A
Absorption / floatfactory default 57.6 / 55.2 V, range 36–60 V
Enclosure
steel, IP21, protection class I
Dimensions / weight
425 × 440 × 125 mm, 11 kg
Operating temperature
−40 to +65 °C (datasheet)
Battery / AC
M8 bolts / 10 mm² terminals
PV
2 × MC4 positive, 2 × MC4 negative
Communication
VE.Can, VE.Direct, Bluetooth

The documents differ in a few places: continuous power at 25 °C (datasheet 4,800–5,300 W, manual table 4,600–5,200 W), operating temperature (datasheet and manual table up to +65 °C, sections 3.1 and 6.8.2 of the manual and the product page — 60 °C, full solar power up to 40 °C) and minimum PV voltage for continued operation (65 V or 80 V). The manual table also lists “88 A from AC”, although the unit has no AC input.

Typical setup

Where Inverter RS Smart Solar sits in the system

Panels on the MPPT input, 48 V battery through a fuse, 230 V loads on the output. Hover over or tap a diagram element. Illustrative diagram.

VE.Can PV panels Inverter RS Smart Solar 230 V loads PV inverter (optional) 48 V battery DC fuse GX device
direct current (DC)alternating current (AC)communication
Hover over the diagram element or tap it.
  1. Panels → MPPTVoc < 450 V and < 8 × float; original MC4 only.
  2. 230 V outputLoads; never grid or generator.
  3. PV inverter (optional)AC-coupling up to 5,000 W, 1:1 rule.
  4. Battery → fuse35 mm² and 125 A up to 2 m, 70 mm² and 200 A up to 5 m.
  5. GX (VE.Can)Monitoring and VRM; strongly recommended if you have several units.
Panels

PV connection rules

Voc lower than 8 × float

The open-circuit voltage of the array must be lower than eight times the battery float voltage — at a float voltage of 54.0 V, that is 432 V. If this is exceeded, the unit reports “Over-charge Protection” and shuts down. Remedy: a higher float voltage or fewer panels in the string.

  • No more than 450 V — overvoltage damages the charger and is not covered by the warranty. In winter Voc rises: the manufacturer recommends the MPPT calculator and a 10% margin.
  • Reversed connection of an array with a short-circuit current above 16 A voids the warranty. Reverse PV polarity gives no message — charging current is zero and the unit heats up.
  • Only original Stäubli MC4 connectors; panels of the same brand, type and model; no optimisers.
  • Class A modules to IEC 61730 (non-isolated inverter on the AC side). The + and − conductors of the array insulated from earth, array frame earthed; in the system only one point connected to earth — at the battery.
Inverter RS Smart Solar with open base — MC4 PV input connectors
PV voltage measurement only by a trained PV electrician, with the unit and PV isolator switched off; MC4 is disconnected with the proper tool, and the measurement is taken with insulated MC4 test leads. PV cables remain live at high voltage even after disconnection from the inverter.
Which model

Inverter RS Smart Solar, Inverter RS Smart or Multi RS Solar?

This sheet

Inverter RS Smart Solar

An inverter with built-in MPPT — off-grid, where the battery is charged by panels. No AC input and no mains charger.

48 V · 6 kVA · MPPT 450 V
Without MPPT

Inverter RS Smart

The same inverter without a controller — PV via a separate MPPT or a PV inverter on the AC output. Inverter RS datasheet.

48 V · 6 kVA
With mains charger

Multi RS Solar

AC input comes from the mains or generator, and a charger. Multi RS Solar card · Multi RS19 Solar. Connecting Inverter RS and Multi RS in one system is currently unsupported.

+ AC input + charger
Installation

Installation rules

High voltage even when switched off

There may be 400–500 V DC inside even after switch-off. Disconnect the battery, PV isolator and other sources, then wait at least 5 minutes. Do not remove the front cover. Installation only under the supervision of a qualified installer; cover the panels during installation.

Protection class I — earthed enclosure

The AC output terminals or the earthing point on the enclosure must have a permanent earth connection; in a vehicle the enclosure is connected to the chassis, on a boat — to the hull or grounding plate. The conductor from the enclosure terminal to earth must be at least the same cross-section as the PV conductors. If earth damage is suspected, switch the unit off and secure it against restart.

  • Sequence: 1) check polarity and battery, 2) remote, relay and communication, 3) check polarity and PV array.
  • Location: vertical, 30 cm above and below the unit, on a non-combustible surface, away from sun, moisture, soot, dust and salt, and away from flammable or corrosive gases and vapours. Never directly above lead-acid batteries.
  • Battery terminals: lug, flat washer, spring washer, nut — max 14 Nm; do not loosen the lower nut soldered to the board. AC terminals: 1.2 Nm.
  • Battery and PV cables: flexible Class 5 copper stranded wire (single strand max. 0.4 mm), insulation min. 90 °C; voltage drop on the battery cables above 2.5% is not acceptable.
Inverter RS Smart Solar with open connection compartment — fans, battery and AC terminals, PV inputs
Battery terminals on the left-hand side of the compartment. HB flammability class batteries or better, isolator on the AC and DC side, protection between the battery and the inverter — always.
Cable lengthCross-section per poleDC fuseMinimum battery
0–2 m35 mm²125 A200 Ah lead-acid or 50 Ah lithium
2–5 m70 mm²200 A

You must not connect the inverter output to the mains or a generator. AC terminals 10 mm², maximum output fuse 30 A, an RCD type A may be used — the built-in relay connects the output N to the enclosure so the RCD works. The manual does not specify the recommended AC cable cross-section or TN/TT earthing systems. More: earthing and RCD.

Settings

How to set it up

Set up in VictronConnect over Bluetooth (range about 20 m, one phone at a time) — on Windows via the VE.Direct–USB interface. If you lose the PIN, use the PUK code from the sticker to reset it to 000000.

  • Battery: 48 V fixed voltage; presets Normal, High and LiFePO4 2-wire BMS; for LiFePO4, charging is blocked below 5 °C. Lithium is not equalised; turn off temperature compensation for lithium.
  • BMS: Remote mode “2-wire BMS” — Remote H disables the inverter (allow to discharge), Remote L disables charging from PV (allow to charge). In this mode the unit will not start without a BMS; the manufacturer recommends smallBMS with Victron batteries.
  • DVCC and BMS-Can override the charger settings — you can see this in VictronConnect and GX; this is not a fault.
  • Dynamic cut-off (disabled by default) — do not enable it when other loads are connected to the same battery.
Inverter RS Smart Solar right side
Settings in the app. The Remote L–H bridge (installed by default) is on the I/O terminal strip in the connection compartment; remote on/off works only when the main switch is in the “on” position.

Parallel and three-phase operation (VE.Can, terminators at both ends): up to 12 units, in three-phase the same number on each phase, at most 4 per phase, star only; one common battery bank; each unit separately protected on AC and DC. Set the settings in each unit. Configure system mode before connecting loads — the AC output then disappears for a few seconds. Do not enable “Continue with missing phase” with three-phase loads. The manufacturer notes that these systems are not for inexperienced installers; in one place the manual also contradictorily states “one unit per phase”.

Limitations

What the Inverter RS Smart Solar does not do

The manual does not have a separate section on limitations (although it refers to one in the data table) — below are the limitations collected from the full text.

No AC input

There is no mains charger or source transfer switch. Generator — via a separate battery charger.

AC coupling up to approx. 95%

With a PV inverter on the output, the battery will not charge to 100% — full charging requires PV modules on the MPPT.

Charging up to 100 A

Total current from PV and AC coupling; above 60 V battery voltage drops linearly to 5 A at 62 V.

No VE.Smart

It does not work with the VE.Smart network (for example, Smart Battery Sense). GX only via VE.Can.

No split-phase and delta

Single-phase or three-phase in star. Connection with Multi RS is currently not supported — according to error 70 description, newer Inverter RS units may support it; check with your supplier.

No battery reverse-polarity protection

Reverse battery connection is not protected and is not covered by the warranty.

Diagnostics

Most common faults

Typical situations from the manual. You can check the error number from the display or VictronConnect in the RS device error codes section — the manual includes a general list of MPPT codes.

No response, blank display

Check the main switch (bottom, left) and PV isolator (bottom, centre), voltages, cables and fuses. If needed, charge the battery from another source.

MPPT not charging

Start requires 120 V at the PV input. In VictronConnect, “Why is the charger off?” will show the cause: too little PV, shut-down from the BMS, low lithium battery temperature.

The inverter has shut down AC output, MPPT is charging

PV module insulation resistance too low. Do not touch metal parts, call a technician; check PV cables and connectors.

PV safety relays have operated

The relay flag shows “!”, the green LED on the board is off, the PV array is short-circuited. Do not try to reset it — return the unit to the supplier.

Shuts down under overload

After three restarts within 30 s it remains off — disconnect the load, switch the unit off and on.

Shuts down on low battery

After three cycles it stops trying, but the MPPT keeps charging; after 4 shutdowns it will switch on itself when the voltage stays above “Charge detect” for 30 s.

Battery not fully charged

Too little PV (check the 30-day history — does it reach float), load too high, voltage drop on the cables above 2.5%, or incorrect temperature compensation.

Burnt MC4 connectors

Rigid or soldered conductors, cable too thin, over 30 A per pair of connectors, or poorly crimped MC4s — usually not covered by warranty.

Full power not achievable

PV array too small or temperature above 40 °C — full solar power up to 40 °C. In a cabinet, provide air inlets and outlets.

Questions

Most common questions about the Inverter RS Smart Solar

Can I charge the battery from the mains or a generator?

Not directly — the Inverter RS Smart Solar has no AC input. The manufacturer specifies a separate battery charger with a generator. For charging from the mains or a generator, use Multi RS Solar.

How many panels can I connect?

According to the datasheet, two inputs of 3 kW each (6 kW total), 12 A working current per tracker. String Voc below 450 V and below 8 × battery float voltage. First check which version you have — see two MPPT versions.

Which fuse and cable for the battery?

Up to 2 m: 35 mm² and 125 A fuse; from 2 to 5 m: 70 mm² and 200 A. Minimum battery: 200 Ah lead-acid or 50 Ah lithium.

How many inverters can I connect?

Up to 12 in parallel via VE.Can; in a three-phase system the same number on each phase, at most 4 per phase. You can connect solar and non-solar versions; connection with Multi RS is currently not supported.

Can I add a PV inverter on the output?

Yes, up to 5000 W, while keeping the 1:1 rule and the minimum battery size from the AC Coupling manual. The Inverter RS limits the PV inverter by raising frequency (stop at 53.2 Hz); the setup was tested with Fronius (MG50/60). The battery will then charge to about 95%.

How do I connect to Cerbo GX?

Only via VE.Can (with terminators). The VE.Direct port supports GlobalLink 520 or a computer via VE.Direct–USB.

The unit does not switch on — what should I check?

Main switch on the bottom left, Remote L–H bridge on the I/O terminal strip, Remote mode (in “2-wire BMS” it will not start without a BMS) and battery voltage — start from 41 V.

How is it different from the Inverter RS Smart?

It has a built-in MPPT charge controller, PV isolator and module insulation monitoring. The inverter section has mostly the same parameters — differences include output short-circuit current (45 A in the Solar datasheet), additional solar power up to 5800 W and AC-coupled charging up to about 95%. Inverter RS Smart datasheet.

Content checked against Victron Energy documentation (datasheets and manuals) — as of 22 September 2026. Report a content error · Revision log