Tip Set the input current limit according to the shore power protection — MultiPlus-II 3 kVA lets you go down to 4 A, the 5 kVA model to 6 A.
Victron Help Centre
Tool

Campsite current limit

Enter the shore power protection, inverter/charger model and load power. We will suggest the input current limit and calculate how much power the shore supply gives, how much PowerAssist adds from the battery and what current will charge the battery.

4 Alowest input limit of MultiPlus-II 3 kVA
6 Alowest input limit of MultiPlus-II 5 kVA
13 APowerAssist adds in the 3 kVA model
45 Aat output with 32 A from mains (32 + 13)
Digital Multi Control panel with input current limit knob
1Shore powershore power protection — ask the campsite staff
A
2Inverter/chargerbattery model and voltage
Battery voltage
3230 V loadstotal power of devices running at the same time
W
Quickly:

The powers under “Quickly” are typical values — check the appliance nameplates.

How we calculate

Assumptions

Input limit: you set it according to the shore power or generator protection. Ranges from the manual: MultiPlus-II 3 kVA 4–32 A, 5 kVA 6–50 A (larger 8–15 kVA models from 11 A), classic MultiPlus 3000 VA 2.3–16 A or 5.3–50 A depending on the switch. If the shore supply has lower protection than the device’s minimum, you cannot set the limit low enough.

PowerControl: the charger takes only the current left over after the loads. We calculate charge current from the spare shore power: (shore power − loads) × 0.9 ÷ charge voltage (14.4 / 28.8 / 57.6 V), up to the charger current in the model name.

PowerAssist: when the loads need more, the inverter adds power from the battery — up to its rated power. Example from the MultiPlus-II 3 kVA manual: it adds 13 A, so with a 32 A limit the output will be 45 A. For the 5 kVA model we calculate similarly, about 21 A (5000 VA ÷ 230 V).

The full explanation with diagrams is in the guide How to choose an inverter/charger and PowerAssist. If the inverter still shuts down: MultiPlus reports overload and MultiPlus does not accept mains.

Sources

Content checked against Victron Energy documentation (datasheets and manuals) — status as of 23 September 2026. Report an error in the content · Correction log